IC695CMM002 and IC695CMM004, PACSystems RX3i Serial Communications Modules (GFK-2461) ka36N000000k9vcQAA | Emerson Customer Center

IC695CMM002 and IC695CMM004, PACSystems RX3i Serial Communications Modules (GFK-2461)

Description, specifications, installation instructions, and release information for the PACSystems RX3i Serial Communications Modules.
 

Errata:
                                                                                                                                                                                                                                       
PageSectionChange and/or UpdateDate
2--GFK-2975 does not exist. This should point to the CMM Manual GFK-2460.07-04-23
    
  • Attached Files

  • GFK-2461U_CMM002_004_IPI.pdf

    Posted: 3/10/2023

    GFK-2461U: Reduces the frequency of SPL script halts on EXREAD and/or EXWRITE w/ mail timeout error. HW Control (RTS/CTS) works on v1.34 modules and does NOT work on v2.0 modules. SPL TIMER and ELAPSED functions may in rare instances return a negative value

  • GFK-2461T_CMM002_CMM004_IPI.pdf

    Posted: 9/13/2022

    GFK-2461T - Product labels have been updated to show compliance with new certifications. For updated certifications, please refer to https://emerson-mas.force.com/communities/en_US/Article/Certifications-and-Agency-Approvals-Landing-Page

  • GFK2461R-CMM002_CMM004_IPI.pdf.pdf

    Posted: 8/3/2022

    GFK-2461R - This FW change fixes a DNP3 Time and Date word swap issue. In DNP3 mode, a write operation for the Time and Date Target Object results in swapped words and bytes relative to V1 units. This issue was introduced with FW v2.00 and is corrected with FW v2.12. Following Emerson’s acquisition of this product, changes have been made to apply appropriate branding and registration of the product with required certification agencies. No changes to the material, process, form, fit, or functionality